ProLiant DL380 G8 (642105-421) - Power Not Redundant PDS Warning

$
0
0

I'm having a problem with the System Information in the iLO showing the Power Status as:  Not Redundant.

When you click on Power for more information it says:

 

Bay 1:  Good, In Use   ...  PDS:  NO

Bay 2:  Good, In Use  ...   PDS: Yes

 

 

  The only thing I could find on my searches says that both power supplies are probably plugged into the same PDU (which they are, there is only one PDU at the small site). 

 

  The server is in a remote site, and I can't get the server turned over with this error/warning showing...  Is this always a case of the power being plugged into the same PDU?  I'm not even sure if they have an iPDU over there.   Both power supplies are plugged in, and both power supplies are good and "In Use" but the PDS: No  is what is causing the fuss. 

 

  Is there a way to turn off checking or something?

 